Rated characteristics of Electrical Contactors
Rated characteristics of Electrical Contactors
1. Rated values of voltages:
(i) Rated voltage (Operational voltage)
For a three phase contactors, the voltage between phases is called rated voltage or operational voltage. (ii) Rated Insulation Voltage The voltage, on which performs the dielectric test.
For a three phase contactors, the voltage between phases is called rated voltage or operational voltage. (ii) Rated Insulation Voltage The voltage, on which performs the dielectric test.
2. Rated Values of Current:
(i) Rated Thermal Current
The maximum current, on which a Contactor operates continuously for eight (8) hours without increasing the temperature (increased with a permissible limit).
(ii) Rated Operational Current
A Manufacturer tells the rated operational current considering Contactors rated frequency, operational voltages, rated duty and utilization factor.
5. Rated duty and Serves Conditions:
(i) Eight Hours Duty
A Contactor can carry the normal current for more than 8 hours. The contactors rated thermal current can be found by 8 hours duty.
(ii) Uninterrupted duty
A Contactor can be close for a long time (from 8 hours to many years) without interruption. However, Due to Oxidation and dust on contacts, Temperature may be increased.
(iii) Contactors making Capacity
Contactors rated making capacity is the value of current, on which the contacts of contactor can make the connections (i.e. Contactor can close their contacts) without arcing or melting. A.C contactors making capacity is defined according to the Current Symmetrical Components R.M.S value.
(iv) Contactors Breaking Capacity
Contactors rated breaking capacity is the value of current, on which the contacts of contactor can break the connections (i.e. Contactor can open their contacts) without arcing or melting. A.C contactors breaking capacity is defined according to the Current R.M.S value.
Source : http://www.electricaltechnology.org/2014/07/rated-characteristics-of-electrical-contactors.html
Source : http://www.electricaltechnology.org/2014/07/rated-characteristics-of-electrical-contactors.html
Available link for download
Labels:
characteristics,
contactors,
electrical,
of,
rated
Wednesday, January 11, 2017
Why is electrical power transmitted at low frequencies and not at high frequencies
Why is electrical power transmitted at low frequencies and not at high frequencies
GENERATION
and the frequency is given by :
f= P*N /120
Now to produce voltage at a high frequency , two things have to be increased :
Since the number of poles in this Alternator have increased (compared to two pole High speed turbogenerators rotating at 3000/3600 RPM at 50/60 Hz respectively) , the diameter of the machine will increase which will make the size of machine large.
Now that to produce power at High frequency , you would have to rotate the machine at high speeds which would require higher steam input for same amount of power at a higher frequency.
Higher input to alternator will deteriorate it mechanically. To paraphrase a high frequency alternator needs to be mechanically robust and thus will require a larger size and more material in construction.
TRANSMISSION
While C and G are shunt parameters of line *G being frequency independent*

If the voltage at high frequency is used to transmit power
DISTRIBUTION & UTILIZATION
Even in distribution , the high frequency AC will not be that efficient :
- Power is generated from Synchronous machines (Alternators) which rotate at a particular speed called the synchronous speed given by
and the frequency is given by :
f= P*N /120
Now to produce voltage at a high frequency , two things have to be increased :
- Number of poles in machine
- Speed of machine
Since the number of poles in this Alternator have increased (compared to two pole High speed turbogenerators rotating at 3000/3600 RPM at 50/60 Hz respectively) , the diameter of the machine will increase which will make the size of machine large.
Now that to produce power at High frequency , you would have to rotate the machine at high speeds which would require higher steam input for same amount of power at a higher frequency.
Higher input to alternator will deteriorate it mechanically. To paraphrase a high frequency alternator needs to be mechanically robust and thus will require a larger size and more material in construction.
TRANSMISSION
- Coming to your actual questions about transmission of power at high frequency , We need to realize the model of transmission line
While C and G are shunt parameters of line *G being frequency independent*
If the voltage at high frequency is used to transmit power
- Drop across inductor will increase as V = I*X =I*2*3.14*f*L (f being the frequency).
- A higher drop will cause the line voltage to sag.Hence the coveted flat voltage profile will not be obtained.
- The voltage will decrease with increase in length and it will be less most at the receiving end (where it is needed the most).
- Corona loss is directly proportional to frequency, hence the losses due to corona will increase
- This will cause more interference with communication/telephone lines.
- High losses in transmission wires due to skin effect.
- Because of skin effect , the cost of conductor material will increase as the conductor is not utilized fully at high frequencies.
- Economy of transmission is a major point while designing transmission lines . increasing the cost of conductor will make the system uneconomical
- Since the resistance due to skin effect increases ( assume Rac=1.6Rdc), line losses (I^2R ones) will increase and hence the power transmission capability will decrease
- FACTS devices or compensators will be required for reactive power demand/supply making the system even more costly.
DISTRIBUTION & UTILIZATION
Even in distribution , the high frequency AC will not be that efficient :
- We use a lot of power electronic devices. A high frequency will cause large switching losses.
- Harmonics of higher frequencies being fed back to grid , filter requirements might be there.
- Poor voltage regulation
- Possibility of thermal noise/shot noise /white noise (high frequency ) interference with home appliances
Available link for download